| Rated permanent current Iu, A | 3200 |
| Number of poles | 3 |
| Overload release current setting, A | 1280...3200 |
| Number of auxiliary contacts as change-over contact | 6 |
| Rated voltage, V | 400...690 |
| Degree of protection (IP) | IP20 |
| Position of connection for main current circuit | Back connection |
| Type of electrical connection of main circuit | Bolt connection |
| Type of control element | Push button |
| Rated short-circuit breaking capacity lcu at 400 V, 50 Hz, kA | 100 |
| Suitable for DIN rail (top hat rail) mounting | No |
| Integrated earth fault protection | Yes |
| With under voltage release | No |
| Device construction | Built-in device slide-in technique (withdrawable) |
| Complete device with protection unit | Yes |
| Type of product | Выключатель автоматический воздушный |
| Motor drive integrated | Yes |
| Number of auxiliary contacts as normally open contact | 6 |
| Number of auxiliary contacts as normally closed contact | 6 |
| Rated current In | 3200А |
| Breaking Capacity Limit at Ue 400V, Icu | 100 kA |
| Breaking Capacity Limitat Ue 690V, Icu | 85 kA |
| Type of contactors | M |
| Q'ty of poles | 3P |
| Execution | Withdrawable |
| Executing the connection method | Horizontal |
| Product/component type | Air circuit breaker |
| Series | YON pro |
| Release name | Electronic |
| Type release | ETH |
| Motor drive | 220 В AC |
| Switching coil | 220 В AC |
| Shunt coil | 220 В AC |
| Undervoltage release | No |
| Warranty | 5 years |