Code: ANX06NS4FH522200K
Code: ANX06NS4FH522200K
  • To ask a question
Rated permanent current Iu, A 630
Number of poles 4
Overload release current setting, A 252...630
Number of auxiliary contacts as change-over contact 6
Rated voltage, V 400...690
Degree of protection (IP) IP20
Position of connection for main current circuit Back connection
Type of electrical connection of main circuit Bolt connection
Type of control element Push button
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz, kA 66
Suitable for DIN rail (top hat rail) mounting No
Integrated earth fault protection Yes
With under voltage release No
Device construction Built-in device fixed built-in technique
Complete device with protection unit Yes
Type of product Выключатель автоматический воздушный
Motor drive integrated Yes
Number of auxiliary contacts as normally open contact 6
Number of auxiliary contacts as normally closed contact 6
Rated current In 630 A
Breaking Capacity Limit at Ue 400V, Icu 66 kA
Breaking Capacity Limitat Ue 690V, Icu 50 kA
Q'ty of poles 4P
Execution Стационарный
Executing the connection method Oriented
Type release ETA
Integrated accessories: Motor drive, closing coil, shunt trip, 220 V AC control